KIRLOSKAR ELECTRIC COMPANY LTD Designs, Manufactures, Markets and Services Rotating machines, dedicated to control of the Motive force for operation of Industrial machinery, Power Generation and control equipment for T&D Industry. Kirloskar has always been known for creating unique solutions for any kind of customized applications relating to Industrial Power and Electrical Control Equipment.

Vaccum Circuit Breaker

VCB Features:

  • Maintance free design.
  • Horizontal Drawout and Isolation.
  • Positive racking mechanism.
  • Interlocks to prevent insertion / withdrawal of closed CB.
  • CB can operate in test or service position only.
  • Identicaly rated CBs are fully interchangable.
  • Easy retro fitting with Cassete System.
  • Fully type tested as per IEC60056 / IS 13118 / IEC 62271-100.
  • Available range 11kV, 22kV and 33kV


Operating Mechanism:

  • Proven Spring operated Mechanism.
  • Designed to closed and latch.
  • Manual / Motorised Option.
  • In built trip free mechnism.
  • In built anti pumping feature.
  • Mechanical ON/OFF indication.

Specification:

11kV22kV33kV
TypeVCBC500VRK 12-14VRK 24VRK 36
Rated VoltageKV12122436
Insulation levelkVrms/kVp28/7528/7550/12570/170
Rated CurrentA1250250016001600
Braking CapacitykA26.2404026.2
Making CapacitykAp65.510010078.75
Short Time Current (1 or 3 Sec)kA26.2404026.2
Operating SequenceO - 0.3 Sec - CO - 3 min - CO
Auxiliary Switch Contacts8NO + 8NC
Spring Charging Motor PowerW250
Spring Charging Motor VoltageV230V AC, 110V DC, 220V DC
Closing / Tripping Coil PowerW180
Closing / Tripping Coil VoltageV24, 30, 48, 110, 220DC
Weight (approx)KG150140140360


SF6 Circuit Breakers

SF6 Circuit Breaker Features:

  • Even in the event of complete gas leak, our SF6 CBs are capable of breaking 100% normal current & with stand system voltage
  • Advance warning of gas leak by continuous preassure monitoring.
  • Explosion proof and FAIL - SAFE CB by means of saftey membrane for each pole.
  • Inbuilt interlocks for prevention of withdrawing / Insertion of closed CB. Operation of CB is possible only in Test, Service or Isolated position.
  • Automatic Safety shutters to cover live parts when CB is withdrawn.
  • No degradation of main current carrying contacts, as there are seprate current carring and arcing contacts.
  • Our SF6 CBs operate at low preassure. The internal preassure rise at the instant of current interruption also stays low. Due to this and the high dgree of gas tightness adequate for entire life of the breaker os ensured.
  • Available range 11kV, 22kV and 33kV



Operating Mechanism:

  • Proven Spring operated Mechanism.
  • Designed to closed and latch.
  • Manual / Motorised Option.
  • In built trip free mechnism.
  • In built anti pumping feature.
  • Mechanical ON/OFF indication.

Specification:

11kV22kV33kV
TypeFP62DFP63GFP62DFP63GFP62DFP63G
Rated VoltageKV121224243636
Insulation levelkVrms/kVp28/7528/7550/12550/12570/17070/170
Rated CurrentA125012502500250016001600
Braking CapacitykA26.24026.226.21626.2
Making CapacitykAp65.510065.565.54065.5
Short Time Current (1 or 3 Sec)kA26.24026.226.21626.2
Operating SequenceO - 0.3 Sec - CO - 3 min - CO
Auxiliary Switch Contacts8NO + 8NC
Spring Charging Motor PowerW250
Spring Charging Motor VoltageV230V AC, 110V DC, 220V DC
Closing / Tripping Coil PowerW80
Closing / Tripping Coil VoltageV24, 30, 48, 110, 220DC
Weight (approx)KG200225200225225250

top